INSTALLATION CABLES, FLEXIBLE WIRES & CORES

H05V-K / H07V-K / 2491 X

Standards: TS 9758 HD 21.3 S3 VDE 028 1-3 BS 6004
Construction :PVC insulated wires, finely stranded copper conductors.
Application: For protected insulation in equipment and lighting fitting, also for in conduit, on and under plaster.
Application:Rated Voltage U0/U: 300/500 V-450/750V AC test voltage : 2kV 2,5 kV DC test voltage : 5 kV 5 V.
Technical data: Operating temperature 70 ° C
Electrical specifications: Below current carrying capacity for 30 ° C ambient temperature.

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC
resistance at 20 C
ohm/km
Current carrying
capacity in conduit
A
2 x 0,75
6,6
65
26,0
6
2 x 1
6,9
74
19,5
10
2 x 1,5
7,4
90
13,3
15,5
2 x 2,5
9,1
138
7,98
19,5
2 x 4
10,5
180
4,95
26
3 x 0,75
6,9
74
26
6
3 x 1
7,3
86
19,5
10
3 x 1,5
7,9
107
13,3
15,5
3 x 2,5
9,6
163
7,98
19,5
3 x 4
11,5
230
4,95
26
4 x 0,75
7,5
88
26
6
4 x 1
7,9
102
19,5
10
4 x 1,5
8,9
135
13,3
15,5
4 x 2,5
10,9
206
7,98
19,5
4 x 4
12,5
280
4,95
26