INSTALLATION  CABLES,  FLEXIBLE  WIRES & CORES

NVV / NYM / CU-PVC-PVC

Standards: TS 9759 HD21.4 S2 VDE 0250 KISIM/PART 204 BS 6004
Application: In dry rooms, in locations and store rooms subject to fire and explosion hazards, as well as for outdoor use,but not for laying in the ground. For permanent installation clear from or on plaster as well as in or under plaster.
Construction: PVC insulated wire with, finely stranded copper conductors
Electrical specifications: Max.Operating Temperature:70 °C
Voltages: Rated Voltage U/U: 300/500V Test Voltage AC :2kV Test Voltage DC :5kV

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC resistance
at 20 C
ohm/km
Current carrying capacity
in conduit
A
Delivery length
(approx)
2 x 1,5
8,7
127
12,1
15,5
100
2 x 2,5
9,9
11
7,41
19,5
100
2 x 4
11,2
231
4,61
26
100
2 x 6
12,2
291
3,08
34
100
2 x 10
15,4
473
1,83
46
1000
2 x 16
18,4
698
1,15
61
1000
3 x 1,5
9,1
146
12,1
15,5
100
3 x 2,5
10,4
200
7,41
19,5
100
3 x 4
11,8
274
4,61
26
100
3 x 6
13,13
365
3,08
34
100
3 x 10
16,3
575
1,83
46
1000
3 x 16
19,9
88
1,15
61
1000
4 x 1,5
9,8
11
12,1
15,5
100
4 x 2,5
11,2
236
7,41
19,5
100
4 x 4
13,2
342
4,61
26
100
4 x 6
14,5
45
3,08
34
100
4 x 10
1,6
693
1,83
46
1000
4 x 16
22,1
1079
1,15
61
1000
5 x 1,5
11
210
12,1
15,5
100
5 x 2,5
12,6
290
7,41
19,5
100
5 x 4
14,4
400
4,61
26
100
5 x6
15,6
530
3,08
34
100
5 x 10
20,6
870
1,83
46
1000