PVC  INSULATED  LOW  VOLTAGE  POWER  CABLES

YVZV / NYRY

Standards: TS IEC 60502-1 VDE 0271 BS 6346
Construction: PVC Insulated steel wire armoured multi-core cables with copper conductor.
Application: Is most suitable in areas where mechanical damage is a possibility. Can be laid outdoors, indoors, underground and in ducts.
Technical data: Min. Bending Radius : 12 x D Max. Operating Temperature : 70 ° C Max. Short Circuit Temperature : 160 ° C
Voltages: ated Voltage U/U: 0,6/1kV Test Voltage AC :3,5kV Test Voltage DC :8,4kV

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC
resistance at 20 C
ohm/km
Current carrying
capacity in ground
A
Current carrying
capacity in air
A
Delivery length
(approx)
m
4 x 1,5
14,5
420
12,1
26
18,5
1000
4 x 2,5
15,5
500
7,41
34
25
1000
4 x 4
18,5
750
4,61
44
34
1000
4 x 6
19,5
850
1,83
75
60
1000
4 x 10
21
1100
1,83
75
60
1000
4 x 16
25
1650
1,15
98
80
1000
4 x 25
29
2250
0,727
128
106
1000
4 x 35
2
2800
0,524
157
131
1000
4 x 50
38
3850
0,387
185
159
1000
4 x 70
42
4950
0,268
228
202
1000
4 x 95
48
6750
0,193
275
244
1000
4 x 120
52
8100
0,153
313
282
500
4 x 150
57
9600
0,124
399
371
500
4 x 185
62
11700
0,0991
399
371
500
4 x 240
70
14750
0,0754
464
436
500