VC  INSULATED  LOW  VOLTAGE  POWER  CABLES

YVV / NYY-O / NYY- J Control Cables

Standards: TS IEC 60502-1 VDE 0276 IEC 60502
Construction: Multi core PVC insulated cables with solid or stranded copper conductors. PVC inner and outer sheath.
Application: In indoor installation, in cable ducts, outdoors and underground for power stations, industrial plants and switching stations where mechanical damage is expected.
Technical data: Max. Operating Temperature : 70 ° C Max. Short Circuit Temperature : 160 ° C
Voltages: Rated Voltage U/U: 0,6/1kV Test Voltage AC :3,5kV Test Voltage DC :8,4kV

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC
resistance at 20 C
ohm/km
Current carrying
capacity in ground
A
Current carrying
capacity in air
A
Delivery length
(approx)
m
5 x 1,5
13,6
307
12,1
25,0
18,5
1000
7 x 1,5
14,5
360
12,1
15,0
12,0
1000
10 x 1,5
17,5
490
12,1
12,5
10,2
1000
12 x 1,5
17,9
535
12,1
11,9
9,7
1000
14 x 1,5
18,7
590
12,1
11,3
9,3
1000
18 x 1,5
20,4
727
12,1
10,0
8,3
1000
21 x 1,5
21,3
793
12,1
9,3
7,9
1000
24 x 1,5
23,4
898
12,1
8,8
7,4
1000
30 x 1,5
25,0
1070
12,1
8,3
6,9
1000
40 x 1,5
27,6
1332
12,1
7,5
6,5
1000
5 x 2,5
15,2
402
7,41
34
25
1000
7 x 2,5
16,2
476
7,41
20
16,3
1000
10 x 2,5
19,8
658
7,41
17
13,8
1000
12 x 2,5
20,3
725
7,41
16,2
13,1
1000
14 x 2,5
21,2
805
7,41
15,3
12,5
1000
19 x 2,5
23,3
1006
7,41
13,6
11,3
1000
21 x 2,5
24,8
1129
7,41
12,5
10,8
1000
24 x 2,5
27,3
1281
7,41
11,9
10
1000
30 x 2,5
28,8
1504
7,41
11,2
9,4
1000
40 x 2,5
32,4
1931
7,41
10,2
8,8
1000