XLPE  INSULATED  LOW  VOLTAGE  POWER  CABLES

XLPE Insulated Control Cables

Standards: TS IEC 60502-1
Application: Is used as control cable in power stations and factories where signaling is required. Can be laid indoors, outdoors, underground or in ducts.
Technical data: Min. Bending Radius : 12 x D Max. Operating Temperature : 90 ° C Max. Short Circuit Temperature : 250 ° C
Voltages: Rated Voltage U/U: 0,6/1kV Test Voltage AC :3,5kV Test Voltage DC :8,4kV

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC
resistance at 20 C
ohm/km
Current carrying
capacity in ground
A
Current carrying
capacity in air
A
Delivery length
(approx)
m
5 x 1,5
12
230
12,1
21
18
1000
7 x 1,5
13
270
12,1
18
16
1000
10 x 1,5
16
380
12,1
15
13
1000
12 x 1,5
16
450
12,1
14
13
1000
14 x 1,5
17
500
12,1
14
12
1000
19 x 1,5
19
550
12,1
12
11
1000
21 x 1,5
20
600
12,1
11
10
1000
24 x 1,5
22
680
12,1
11
10
1000
5 x 2,5
13
290
7,41
28
24
1000
7 x 2,5
14
350
7,41
24
21
1000
10 x 2,5
16
500
7,41
20
18
1000
12 x 2,5
18
570
7,41
19
17
1000
14 x 2,5
19
620
7,41
18
16
1000
19 x 2,5
21
750
7,41
16
14
1000
21 x 2,5
22
820
7,41
15
14
1000
24 x 2,5
24
950
7,41
14
13
1000