HALOGEN  FREE, FIRE  RESISTANS  CABLES

H03ZZ-F / H05ZZ-F

Standards: HD 21.14 S1
Construction: Flexible halogen free, flame retardant cables with two to four cores with fine stranded copper conductors.
Application:
Used in energy networks in rafineries, high constructions, business centers where there is risk of fire.
Technical data: Max. Operating Temp : 90 ° C
Voltages: Rated Voltage U/U: 300 - 500 V

Rated cross –
section
mm
Overall diameted of cabe
(approx.)
mm
Net weight
(approx.)
kg/1000 m
Conductor DC resistance
at 20 C
ohm/km

Current carrying capacity

 

A

Delivery length
(approx)
2 x 0,75
6,2
55
26
13
100
2 x 1
6,6
70
19,50
15
100
2 x 1,5
7,6
90
13,3
20
100
2 x 2,5
9,2
140
7,98
26
100
2 x 4
10,6
200
4,95
33
100
3 x 0,75
6,5
75
26
13
100
3 x 1
7,2
90
19,5
15,5
100
3 x 1,5
8,5
130
13,3
20
100
3 x 2,5
9,9
190
7,98
26
100
3 x 4
11,4
265
4,95
33
100
4 x 0,75
7,1
90
26
13
100
4 x 1
7,8
120
19,5
15
100
4 x 1,5
9,2
190
13,3
20
100
4 x 2,5
10,9
250
7,98
26
100
4 x 4
12,5
350
4,95
33
100
5 x 0,75
8,0
120
26
13
100
5 x 1
8,6
150
19,5
15
100
5 x 1,5
10,3
215
13,3
20
100
5 x 2,5
12,1
315
7,98
26
100
5 x 4
14,1
450
4,95
33
100